Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Appendix E

ATEX Approved PowerFlex 700S, Phase II Drives in Group II Category (2) Applications with ATEX Approved Motors

Drive Hardware
Configuration

Digital Input 6 must be configured as a Hardware Enable. Ensure that Jumper
P22 on the Main Control Board is set to HW Enable (Pins 2 and 4).`

Operation Verification

At regular intervals during the life of the machine check the protective system for
proper operation. Both channels shall be verified using the table below. How
frequently the protective system is checked is dependent on the safety analysis of
the machine section controlled by the drive.

= HW Enable

= No HW Enable

Jumper P22

1

2

3

4

1

2

3

4

Protective System Status

Drive In

Safe State

Drive In

Safe State

Drive In

Safe State

Drive Able

To Run

Channel Operation

Safe-Off Option

Terminals 1 & 2

No Power Applied

Power Applied

No Power Applied

Power Applied

PowerFlex 700S Phase II

Enable Input

No Power Applied

No Power Applied

Power Applied

Power Applied

Description For Verification

Safe-Off Option

Monitor Contact

Terminals 3 & 4

Closed

Open

Closed

Open

PowerFlex 700S Phase II

Drive Inhibits

Param. 156, Bits 1 & 16

Bit 16 = 1

Bit 1 = 1

Bit 16 = 0

Bit 1 = 1

Bit 16 = 1

Bit 1 = 0

Bit 16 = 0

Bit 1 = 0