Drive Start-Up

Chapter 1

Table 1 - Common Causes of a Start Inhibit

Examine Parameter 156 [Start Inhibits]

Bit

Description

Action

1

No power is present at the Enable Terminal; TB2-16

Apply the enable

2, 3, 4

A stop command is being issued

Close all stop inputs

5

Power loss event is in progress, indicating a loss of the AC input voltage

Restore AC power

6

Data supplied by the power structure EEprom is invalid or corrupt

Cycle the power - if problem persists, replace the power structure

7

Flash Update in Progress

Complete Flash Procedures

8

Drive is expecting a Start Edge and is receiving a continuous signal

Open all start buttons and remove all start commands

9

Drive is expecting a Jog Edge and is receiving a continuous signal

Open all jog buttons and remove all jog commands

10

A conflict exists between the Encoder PPR programming (Par 232 or 242) and the
encoder configuration for edge counts (Par 233, bits 4 & 5)

Verify encoder data and reprogram

11

The drive cannot precharge because a precharge input is programmed and no
signal is present

Reprogram the input or close the precharge control contact

12

Dig

ital

C

onfigu

ra

tio

n

Start input configured but stop not configured

Program Par 825…830 to include a stop button, rewire the drive

Run input configured but control options do not match

Program Par 153, Bit 8 to “0” (2 wire control)

Start input configured but control options do not match

Program Par 153, Bit 8 to “1” (3 wire control)

Multiple inputs configured as Start or Run

Reprogram Par 825…830 so multiple starts, multiple runs or any combination do
not exist

Multiple inputs configured as Jog1

Reprogram Par 825…830 so only (1) is set to Jog1

Multiple inputs configured as Jog2

Reprogram Par 825…830 so only (1) is set to Jog2

Multiple inputs configured as Fwd/Rev

Reprogram Par 825…830 so only (1) is set to Fwd/Rev

14

Invalid Feedback Device for Permanent Magnet Motor Control

Set Par 222 to Value 5 (FB Opt Port0)