150

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Chapter 3

Troubleshooting

For Allen-Bradley Drives Technical Support:

For Automation and Control Technical Support:

85

Position Error

2

(Motion Only)
The value of

Par 769

[Position Error] exceeded the value of

Par 696

[Motn

PositErrTol].

Verify the value in Par 696 [Motn PositErrTol].
Configured with

Par 399

[Position ErrCnfg].

86

Drive Homing

3

When the drive is in Drive Homing mode (

Par 740

[Position Control], bit 24 or

bit 27 is On), the Drive Homing Alarm triggers and the drive moves to a home
position automatically.

Check Par 740 [Position Control], bit14 “Find Home” or
bit 27 “Return Home”.

88

Stahl Optics

3

The Linear Stahl encoder detected a fault.

Par 291

[Lin1Stahl Status] displays

the details of the fault.

Reconnect encoder or replace encoder.

Reconnect option feedback card.

89

Drv Waking

3

The Wake timer is counting toward a value that will start the drive.

92

Ride Thru

3

The Bus voltage has dropped to the Ride-Through level specified in

Par 408

[Power Loss Level].

Check the AC input voltage and the DC bus voltage.

93

+/- 12volt Power Alarm

3

The12V DC control voltage is outside the tolerance range (Alarm). The positive
voltage power exceeds +15.50 V DC. The negative voltage power exceeds -
15.50V DC.

94

Analog In 1 Loss

1

Analog Input channel 1 is lost. For configuration of Analog Input channel 1, see

Par 1093

[Anlg In1LossCnfg].

Check condition of Analog Input channel 1.

Change configuration for parameter 1093 [Anlg

In1LossCnfg].

95

Analog In 2 Loss

1

Analog Input channel 2 is lost. For configuration of Analog Input channel 2, see

Par 1094

[Anlg In2LossCnfg].

Check condition of Analog Input channel 2.

Change configuration for parameter 1094 [Anlg

In2LossCnfg].

96

Analog In 3 Loss

1

Analog Input channel 3 is lost. For configuration of Analog Input channel 3, see

Par 1095

[Anlg In3LossCnfg].

Check condition of Analog Input channel 3.

Change configuration for parameter 1095 [Anlg

In3LossCnfg].

129

Faults Cleared

*

Indicates that all faults have been cleared.

*Informational only.

130

Fault Q Cleared

*

Indicates that the fault queue has been cleared.

*Informational only.

131

Alarm Cleared

*

Indicates that all alarms have been cleared.

*Informational only.

132

Alarm Q Cleared

*

indicates that the alarm queue has been cleared.

*Informational only.

(1) Refer to

Table 5

on page

144

for Fault Type Descriptions.

No.

Name

Type

(1)

Description

Action

Title

Online at…

Allen-Bradley Drives Technical Support

http://www.rockwellautomation.com/literature

or
Call M-F, 7:00a.m. to 6:00p.m. Central STD time:
1.262.512.8176