Par 780, Par 781, Par 782 – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 108: Par 777

Advertising
background image

108

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Chapter 2

Programming and Parameters

770

PositReg Integ

Sets position regulator integral gain as measured from position error to velocity reference. It has gain units of
(per unit velocity/sec) / (per unit position) and is unit compatible with

Par 768

[PositReg P Gain]. An integral

gain of 25 means that a per unit position error of 0.1 sec will effect a 2.5 P.U. speed change per sec.

Note: 1 per unit position is the distance traveled in 1 sec. at base motor speed.

Default:
Min/Max:
Units:

4.0000
0.0000/1000.0000
/S

2

Y

RW Real

771

PositReg Droop

Position Droop limits the low frequency gain of the position regulators integral channel to a value of (1/droop). It
provides a means to fine tune the stability for load mounted feedback devices where lost motion may cause a
problem. Typically, position droop will have a value that is less than (1/position gain), perhaps even zero for
tightly coupled loads. Position droop has a gain value of (per unit position) / (per unit speed). Note: 1 per unit
position is the distance traveled in 1 sec. at base motor speed.

Default:
Min/Max:

0.0000
0.0000/0.2500

Y

RW Real

772

XReg Integ LoLim

The negative limit of the position regulator integral gain.

Default:
Min/Max:
Units:
Scale:

-176.4000
-14112.0000/0.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

773

XReg Integ HiLim

The positive limit of the position regulator integral gain.

Default:
Min/Max:
Units:
Scale:

176.4000
0.0000/14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

774

XReg Integ Out

The output of the position regulator integral channel after application of the limits. This output is set to zero if
the integral gain is set to zero or the integrator is not enabled.

Default:
Min/Max:
Units:
Scale:

0
-/+14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

RO Real

775

XReg Spd LoLim

The negative speed limit of total position regulator output. Point to point mode uses this parameter to set the
reverse speed reference.

Default:
Min/Max:
Units:
Scale:

-176.4000
-14112.0000/0.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

776

XReg Spd HiLim

The positive speed limit of total position regulator output. Point to point mode uses this parameter to set the
forward speed reference.

Default:
Min/Max:
Units:
Scale:

176.4000
0.0000/14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

777

PositionFdbk Sel

Enter a value to select the position control feedback device. The feedback device used for position control may be
an independent selection from the motor speed control feedback device in

Par 222

[Mtr Fdbk Sel Pri] or

Par 223

[Mtr Fdbk Sel Alt]. If the position feedback is to be the same as the motor feedback, select option 3 “Motor Fdbk”.
This option will set the selected feedback of Par 222 [Motor Fdbk Sel Pri] or Par 223 [Mtr Fdbk Sel Alt] as the
position regulators position feedback.

Notes: Options 5 and 6 are only available when compatible feedback option card is installed. This parameter was
changed to non-linkable for firmware version 3.001.

Default:

Options:

0 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =

“Encoder 0”

“Encoder 0”

7 = “SL DirIntRx0”

“Encoder 1”

8 = “SL DirIntRx1”

“Reserved”

9 = “SL DirIntRx2”

“Mtr Fdbk Pri”

10 = “SL DirIntRx3”

“Motor Sim”
“FB Opt Port0”
“FB Opt Port1”

778

X Notch Attenu

Sets the depth for the Position Notch Filter. Attenuation is the ratio of the output to the input at the notch
frequency. An attenuation of 30 means that the notch output is 1/30th of the input at the specified frequency.
Calculation: Attenuation = Input / Output

Default:
Min/Max:

50
0/500

Y

RW Real

779

X Notch FiltFreq

Sets the center frequency of the Position Notch Filter.

Default:
Min/Max:
Units:

0.0
0.0/500.0
Hz

Y

RW Real

780

PositDetct1 Stpt

Provides the set point for Position Watch 1. Position Watch 1 is enabled and configured with

Par 740

[Position

Control] bits 16 & 17. Position Watch 1 compares this value with

Par 784

[Posit Dect1 In] and sets bit 8 “Posit

Watch1” of

Par 741

[Position Status] when the appropriate condition is satisfied.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

781

PositDetct2 Stpt

Provides the set point for Position Watch 2. Position Watch 2 is enabled and configured with

Par 740

[Position

Control] bits 18 & 19. Position Watch 2 compares this value with

Par 785

[Posit Dect2 In] and sets bit 9 “Posit

Watch2” of

Par 741

[Position Status] when the appropriate condition is satisfied.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

782

In Posit BW

Sets the overall bandwidth of the In Position detector. The detector sets bit 10 “In Position” of

Par 741

[Position

Status], when

Par 769

[Position Error] is within this bandwidth for a sufficient time, specified by

Par 783

[In Posit

Dwell]. A modest hysteresis count is added to the position bandwidth after the position error is within specified
limits.

Default:
Min/Max:

200
0/1000000

Y

RW 32-bit

Integer

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Freq (Hz)

Attenuation

Advertising