Troubleshooting

Chapter 3

26

Ground Fault

1

A current to earth exceeds 35% of the peak drive rating.

Check the motor and external wiring to the drive output
terminals for a grounded condition.

27

Inst Overcurrent

1

The instantaneous motor current exceeds 214% of the rating.

Reduce the mechanical load.

Check the motor and external wiring to the motor.

28

VPL/MC Comm Fail

1

A communication failure has occurred between the Velocity Position Loop
(VPL) processor and the Motor Control (MC) processor on the main control
board. Possible cause are:

The VPL is flashing the MC firmware into the MC processor when HIM

indicates “Loading Config”.

The MC has failed to complete or pass diagnostic tests.

The MC has not detected VPL handshake activity for over 32 ms.

The VPL has not detected MC handshake activity for over 32 ms. This is

indicated when Fault Test Point 15 or 16 equals 1. This test point is viewed
in

Par 330

[Fault TP Data] when

Par 329

[Fault TP select] is set to value 15

or 16.

Cycle power to the drive.

Reflash the firmware.

Replace the Main Control board.

29

PWM Signal Short

1

This fault is detected when ever the actual IGBT gate is different than the
commanded IGBT states. This fault is detected by the Motor Control (MC)
processor.

30

MC Firmware

1

One of the following Motor Control (MC) firmware errors has occurred:

MC Task Over Run

Illegal Interrupt

Self Diagnostic Fault

Data Error

Cycle power to the drive.

Reflash the firmware.

Replace the Main Control board.

31

Precharge Error

2

The precharge function has failed to complete within 30 seconds (default) of
the precharge request. The precharge time out is configurable in

Par 410

[PreChrg TimeOut].
A precharge request is initiated when the DC Bus voltage is above the
Undervoltage Trip level and the precharge input is high (the requirement for
the precharge being high can be bypassed by setting

Par 411

[PreChrg

Control], bit 01 “PreChrg Enable” to 0 “Off”).

Verify the value in

Par 410

[PreChrg TimeOut].

Verify the bit value in

Par 411

[PreChrg Control] = 1

“Enbl PrChrg”.

Configured with

Par 381

[PreChrg Err Cnfg]

32

PWM Asynch

1

The Motor Control Processor is not synchronized with SynchLink.

33

+/- 15volt Power

1

The12V DC control voltage is outside the tolerance range. The positive voltage
power must be within the band from +17.00 to +11.61V DC. The negative
voltage power must be within the band from -17.00 to -11.61V DC.

Replace switch mode power supply. For smaller frames,
replace drive.

35

Parameter Chksum

1

The checksum read from the EEPROM does not match the checksum calculated Cycle power to the drive.

Replace the Main Control board.

38

Brake OL Trip

2

The calculated temperature of the dynamic braking resistor is too high. The
temperature is calculated by a thermal model.
If the resistor is internal, the model uses the resistor characteristics stored in
the power structure EEPROM memory.
If the resistor is external, the model uses values of

Par 416

[Brake PulWatts]

and

Par 417

[Brake Watts].

Verify actual temperature of brake:

If hot, wait for the brake to cool.

If cold, cycle power to the drive. If cold, verify that the

values of Par 416 [Brake PulWatts] and Par 417
[Brake Watts] are correct.

Configured with

Par 369

[Brake OL Cnfg].

39

PowerEE CRC Fail

1

The Cycling Ring Checksum (CRC) of the data stored in the Power Board
EEPROM does not match the stored CRC.

Cycle power to the drive.
In frame 9…14 drives, check the communication bus
lines - 10 pin connector on the Main Control board, Fiber
Optic Power Interface board, and fiber optic cable
connections.

40

SLink Mult Oflow

2

A SynchLink Multiplier Overflow has occurred.

Par 927

[SL Mult State] displays

SynchLink multiplier overflow errors.

Configured with

Par 390

[SL MultErr Cnfg].

41

Ridethru Timeout

1

The drive has been in a bus loss ridethrough condition for more than two
seconds (default). The ridethrough timeout is configurable in

Par 407

[Power

Loss Time].

Verify the AC Line.

Verify the value in Par 407 [Power Loss Time].

42

DC Bus Undervolt

2

The Bus voltage has fallen below the level configured in

Par 409

[Line

Undervolts].

Verify the AC Line.
In frames 1…4 and 9…14, verify that the precharge
resistor is present (with power off, there should be a
resistance between DC+ and BR+).
In frames 5 & 6, check the precharge board for errors. See
the precharge board LED for fault sequence.
Configured with

Par 393

[BusUndervoltCnfg].

No.

Name

Type

(1)

Description

Action