Chapter 2

Programming and Parameters

299 Elapsed

MWHrs

Displays the total energy the drive has consumed or produced. Calculated from the absolute magnitude of the
product of motor speed and motor torque (power), accumulated over time. This value will increase in both regen
and motoring modes of operation. This parameter value can be changed (written to) by the user.

Default:
Min/Max:
Units:
Scale:

0.0
0.0/429496736.0
MWhr
x 10

RW 32-bit

Integer

300

Motor Spd Fdbk

Displays measured motor speed information from the selected feedback device.

Default:
Min/Max:
Units:
Scale:

0.0000
-/+14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

RO Real

301 Motor

Speed

Ref

Displays the speed reference value, after the limit function. This is the input to the error calculator and speed
regulator.

Default:
Min/Max:
Units:
Scale:

0.0000
-/+14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

RO Real

302

Spd Reg PI Out

Displays the output of the speed regulator. This is the input to torque control. A value of 1.0 represents base
torque of the motor.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO Real

303 Motor

Torque

Ref

Displays the reference value of motor torque. The actual value of the motor torque is within 5% of this value.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO Real

304 Limit

Status

Displays the limit status of conditions that may be limiting the current reference or torque reference.
• Bit 0 “+MCS Iq Lim” indicates that torque producing current is at its positive limit.
• Bit 1 “+MCS Ws Lim” indicates that flux producing torque is at its positive limit.
• Bit 2 “0 Ia from +” indicates that torque producing current is limited to zero from the positive direction - refer to

Par 353

[Iq Actual Lim].

• Bit 3 “+Iq Calc” indicates the calculation for torque producing current has reached its positive limit.
• Bit 4 “+Current Lim” indicates that the current reference has reached the positive Motor Current Limit set by

Par 356

[Mtr Current Lim].

• Bit 5 “+DriveProtOL” indicates that the current reference has reached the positive current limit set by the Open Loop Inverter Overload, shown in

Par 343

[OL OpnLp CurrLim].

• Bit 6 “+DriveProtCL” indicates that the current reference has reached the positive current limit set by the Closed Loop Inverter Overload, shown in

Par 344

[OL ClsLp CurrLim].

• Bit 8 “+Torq Limit” indicates that the torque reference has reached the Positive Torque Limit set by

Par 125

[Torque Pos Limit].

• Bit 9 “Mtrng PwrLim” indicates that the torque reference is being limited by the Motoring Power Limit set by

Par 127

[Mtring Power Lim].

• Bit 10 “+Torq CurLim” indicates that current reference has reached the Actual Torque Producing Current Limit set by Par 353 [Iq Actual Lim].
• Bit 11 “Atune Tq Lim” indicates that the torque reference is being limited by

Par 129

[Atune Trq Ref].

• Bit 12 “+0 Torq Ena” indicates that the torque reference is limited to zero because

Par 157

[Logic Ctrl State] bit 9 “Torq Ref En” is off.

• Bit 13 “+0 Curr Ena” indicates that the current reference is limited to zero because Par 157 [Logic Ctrl State] bit 11 “CurrRef En” is off.
• Bit 14 “Speed Limit” indicates the collective status of all speed limitations.
• Bit 15 “Current Lim” indicates the collective status of all current limitations
• Bit 16 “-MCS Iq Lim” indicates that torque producing current is at its negative limit.
• Bit 17 “-MCS Ws Lim” indicates that flux producing torque is at its negative limit.
• Bit 18 “0 Ia from -” indicates that torque producing current is limited to zero from the negative direction - refer to

Par 353

[Iq Actual Lim].

• Bit 19 “-Iq Calc’ indicates the calculation for torque producing current has reached its negative limit.
• Bit 20 “-Current Lim” indicates that the current reference has reached the negative Motor Current Limit set by

Par 356

[Mtr Current Lim].

• Bit 21 “-DriveProtOL” indicates that the current reference has reached the negative current limit set by the Open Loop Inverter Overload, shown in

Par 343

[OL OpnLp CurrLim].

• Bit 22 “-DriveProtCL” indicates that the current reference has reached the negative current limit set by the Closed Loop Inverter Overload, shown in

Par 344

[OL ClsLp CurrLim].

• Bit 24 “-Torq Limit” indicates that the torque reference has reached the Negative Torque Limit set by

Par 126

[Torque Neg Limit].

• Bit 25 “Regen PwrLim” indicates that the torque reference is being limited by the Regenerative Power Limit set by

Par 128

[Regen Power Lim].

• Bit 26 “-Torq CurLim” indicates that current reference has reached the Actual Torque Producing Current Limit set by

Par 353

[Iq Actual Lim].

• Bit 27 “Bus Reg Tq Lim” indicates the bus voltage regulator is active and limiting the regenerative torque.
• Bit 28 “-0 Torq Ena” indicates that the torque reference is limited to zero because

Par 157

[Logic Ctrl State] bit 9 “Torq Ref En” is off.

• Bit 29 “-0 Curr Ena” indicates that the current reference is limited to zero because Par 157 [Logic Ctrl State] bit 11 “CurrRef En” is off.
• Bit 30 “Torque Limit” indicates the collective status of all torque limitations.
• Bit 31 “Power Limit” indicates the collective status of all power limitations.

305

Mtr Trq Curr Ref

Displays the torque current reference present at the output of the current rate limiter. 100% is equal to 1 per unit
(P.U.) rated motor torque.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO Real

306

DC Bus Voltage

Displays measured bus voltage.
Note: The maximum value was increased from 1000.0000 to 1170.0000 for firmware version 3.001.

Default:
Min/Max:
Units:

0.0000
0.0000/1170.0000
V

RO Real

307 Output

Voltage

Displays RMS line-to-line fundamental motor voltage. This data is averaged and updated every 50 milliseconds.

Default:
Min/Max:
Units:

0.00
0.00/3000.00
V

RO Real

308 Output

Current

Displays measured RMS motor current.

Default:
Min/Max:
Units:

0.00
0.00/10000.00
A

RO Real

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Options

Po

w

er

L

im

it

To

rq

ue

L

im

it

-0 C

urr E

nbl

-0 T

rq Enbl

Bus

Re

g Li

m

-T

rq

C

ur

Li

m

Re

gen P

w

rLi

m

-T

rq

L

im

it

Spd

Reg

O

pen

-D

riv

ePr

otCL

-D

riv

ePr

otOL

-C

ur

re

nt

Li

m

-Iq C

alc

0 Iq fr

om -

-MCS

W

s

Lim

-MCS

Iq

Lim

Cu

rr

en

t L

im

Spe

ed Limit

+0 C

urr E

nb

l

+0 T

rq E

nbl

At

un

T

rq

L

im

+T

rq

C

urLim

Mt

rn

g PwrLim

+T

rq Li

mi

t

+

Sp

dR

eg

Op

en

+D

riv

eP

rotCL

+D

riv

eP

rotO

L

+C

urr

ent Li

m

+Iq Cal

c

0 Iq fr

om +

+MCS W

s Lim

+MCS Iq Lim

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True