Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

111

Programming and Parameters

Chapter 2

807

Anlg In2 Value

Displays the actual input value at Analog Input 2. Analog Input 2 may be configured for voltage or current input
signal. For proper selection of the input signal, the DIP switch S-5 and

Par 821

[Analog I/O Units] must be set to

match. Par 807 [Anlg In2 Value] is multiplied by

Par 808

[Anlg In2 Scale] produce the input to the lead lag filter

function.

Default:
Min/Max:
Units:

0.0000
-/+20.0000
V/mA

RO Real

808

Anlg In2 Scale

Scales the range of Analog Input 2 to the range of

Par 806

[Anlg In2 Data]. Enter the units you want per volt or

mA. For example: If Par 807 [Anlg In2 Value] = 0 - 10V and you enter “6” in this parameter, Par 806 [Anlg In2
Data] will equal 0 - 60V.
Par 807 x Par 808 = Par 806.

Default:
Min/Max:
Units:

0.1000
-/+2200000000.0000
/V or /mA

Y

RW Real

809

Anlg In2 Offset

Applies an offset to Analog Input 2. Use the offset to correct for zero signal errors or to create an offset to the
actual input. The output of the A/D converter is summed with this parameter to produce

Par 807

[Anlg In2

Value].

Default:
Min/Max:
Units:

0.0000
-/+20.0000
V/mA

Y

RW Real

810

AI 2 Filt Gain

Provides the Lead term for the Analog Input 2 filter.

Default:
Min/Max:

1.0000
-/+5.0000

Y

RW Real

811

Anlg In2 Filt BW

Sets the frequency for the Analog Input 2 filter.

Default:
Min/Max:
Units:

0.0000
0.0000/3760.0000
rad/s

Y

RW Real

812

Anlg In3 Data

Displays the scaled final value for Analog Input 3.

Default:
Min/Max:

0.0000
-/+2200000000.0000

RO Real

813

Anlg In3 Value

Displays the actual input value at Analog Input 3. Analog Input 3 is a uni-polar voltage input only and cannot be
configured for current.

Type of Input

= Voltage

Polarity

= Uni-Polar

Resolution

= 10 bit (0 to +1023)

Note: When bit 2 “AI3 Thermstr” of

Par 821

[Analog I/O Units] is set (= 1), this parameter cannot be viewed from

the HIM.

Default:
Min/Max:
Units:

0.0000
0.0/10.0
V

RO Real

814

Anlg In3 Scale

Scales the raw analog input data plus the input offset (if any) to the desired data range. The scaled data for
Analog Input 3 is displayed in

Par 812

[Anlg In3 Data] and is available for usage in the drive. Enter the units you

want per volt. For example: If Par 813 [Anlg In3 Value] = 0 - 10V and you enter “6” in this parameter, Par 812
[Anlg In3 Data] will equal 0 - 60V.
Par 813 x Par 814 = Par 812.
Note: When bit 2 “AI3 Thermstr” of

Par 821

[Analog I/O Units] is set (= 1), this parameter cannot be viewed from

the HIM.

Default:
Min/Max:
Units:

0.1000
-/+2200000000.0000
/V

Y

RW Real

815

Anlg In3 Offset

Applies an offset to Analog Input 3. Use the offset to correct for zero signal errors or to create an offset to the
actual input. The output of the A/D converter is summed with this parameter to produce

Par 813

[Anlg In3

Value].
Note: When bit 2 “AI3 Thermstr” of

Par 821

[Analog I/O Units] is set (= 1), this parameter cannot be viewed from

the HIM.

Default:
Min/Max:
Units:

0.0000
-/+20.0
V

Y

RW Real

816

AI 3 Filt Gain

Provides the Lead term for the Analog Input 3 filter.
Note: When bit 2 “AI3 Thermstr” of

Par 821

[Analog I/O Units] is set (= 1), this parameter cannot be viewed from

the HIM.

Default:
Min/Max:

1.0000
-/+5.0

Y

RW Real

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Type of Input:

Configurable, Voltage or Current

Polarity:

Bi-Polar

Resolution:

14 bit (-8191 to +8191)

DIP Switch

Analog I/O Units

AI 2 Voltage

S5-1 = Open

Par 821 Bit 1 = 0 (False)

AI 2 Current

S5-1 = Closed

Par 821 Bit 1 = 1 (True)

Light

Heavy

Par 810

[Al 2 Filt Gain

0.25

0.1

Par 811 [Anlg In2 Filt BW]

50

10