54

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Chapter 2

Programming and Parameters

245

Spd Fdbk TP Sel

Enter or write a value to select the data displayed in

Par 246

[Spd Fdbk TP RPM] and

Par 247

[Spd Fdbk TP Data].

Note: Option values 5 - 15 were changed to “Reserved” and option 41 “First Diff” was added for firmware version
2.004.

Default:

Options:

0 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
15 =
16 =
17 =
18 =
19 =
20 =

“Zero”

“Zero”

21 = “E0 EPR”

“Clock Time”

22 = “E0 Edge Mode”

“InactvFbkDev”

23 = “E0 nMax”

“ActiveFbkDev”

24 = “E0 Error”

“MCP Fdbk Dev”

25 = “E0 Qloss pk”

“Reserved”

26 = “E0 Ploss pk”

“Reserved”

27 = “E0 PlevlHist”

“Reserved”

28 = “E1 Edge Time”

“Reserved”

29 = “E1 dEdge”

“Reserved”

30 = “E1 dTime”

“Reserved”

31 = “E1 EPR”

“Reserved”

32 = “E1 Edge Mode”

“Reserved”

33 = “E1 nMax”

“Reserved”

34 = “E1 Error”

“Reserved”

35 = “E1 Qloss pk”

“Reserved”

36 = “E1 Ploss pk”

“MCP PPR”

37 = “E1 PlevlHist”

“MCP 2^n”

38 = “E0 Delta2Err”

“E0 Edge Time”

39 = “E1 Delta2Err”

“E0 dEdge”

40 = “EOB Present”

“E0 dTime”

41 = “First Diff”

246

Spd Fdbk TP RPM

Displays the value selected in

Par 245

[Spd Fdbk TP Sel] in rpm. This display should only be used if the selected

value is floating point data.

Default:
Min/Max:
Units:
Scale:

0.0
-/+8.0 P.U.
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

RO Real

247

Spd Fdbk TP Data

Displays the value selected in

Par 245

[Spd Fdbk TP Sel]. This display should only be used if the selected value is

integer data.

Default:
Min/Max:

0
-/+32768

RO 16-bit

Integer

249

Fdbk Option ID

Displays information about the Feedback Option.
• Bits 15-11 indicate Module ID Number.
• Bits 10-6 indicate Version Number.
• Bits 5-3 indicate Revision Number High.
• Bits 2-0 indicate Revision Number Low.

Hexadecimal 1000 indicates resolver, hexadecimal 2000 indicates old high-resolution board, and hexadecimal
2040 indicates new high-resolution board.

Options:

250

FB Opt0 Posit

Displays the position feedback (accumulator) from the feedback option card port 0.

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

251

FB Opt0 Spd Fdbk

Displays the speed feedback from the feedback option card port 0.

Default:
Min/Max:
Units:
Scale:

0.0000
-/+14000.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

RO Real

252

FB Opt1 Posit

Displays position feedback (accumulator) from port 1 of the feedback option card.

Default:
Min/Max:

0
0/2147483648

RO 32-bit

Integer

253

FB Opt1 Spd Fdbk

Displays speed feedback from port 1 of the feedback option card.

Default:
Min/Max:
Units

0.0
-/+8.0 P.U.
rpm

RO Real

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

N N NNN

N N NNN

N NNN

Module ID No.

Version No.

Revision No. Low

N NNN

Revision No. High