Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 79

Advertising
background image

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

79

Programming and Parameters

Chapter 2

No.

Name
Description

Values

Li

nk

ab

le

Re

ad

-W

ri

te

Da

ta

T

ype

412

Power EE TP Sel

Enter or write a value to select drive power EEPROM data displayed in

Par 413

[Power EE TP Data]. The default is 0 “Zero”.

Note: Options 74 - 92 were changed and options 93 - 111 were added for firmware version 3.001.

413

Power EE TP Data

Displays the data selected by

Par 412

[Power EE TP Sel].

Default:
Min/Max:

0
-/+2200000000

RO

Real

414 Brake/Bus

Cnfg

Configures the brake and bus operation of the drive.
• Set bit 0 “Brake Enable” to enable the operation of the internal brake transistor.
• Set bit 1 “Brake Extern” to configure the brake to use an external resistor.
• Set bit 2 “Bus Ref High” to select the “high” voltage setting as the turn-on point for the Bus Voltage Regulator. With the “high” setting brake operation starts when bus voltage reaches the value

of

Par 415

[BusReg/Brake Ref], and Bus Voltage Regulator operation starts when bus voltage reaches the value of Par 415 [BusReg/Brake Ref] plus 4.5%. With the “low” setting, the bus

regulator turns on first at the value set by Par 415 [BusReg/Brake Ref] and then the dynamic braking turns on when there are any transients above the value set in Par 415 [BusReg/Brake Ref].

• Set bit 3 “Bus Reg En” to enable the Bus Voltage Regulator. The output of the Bus Voltage Regulator is summed with

Par 128

[Regen Power Lim] and fed into the Power Limit Calculator. It, in

effect, reduces regenerative torque references when the bus voltage is too high.

Notes: This parameter was changed to non-linkable and bits 5 and 6 were added for future use - not active for use with firmware version 3.001. Remove bits 5 and 6 for firmware version 4.001 - not
used.

415 BusReg/Brake

Ref

Sets the “turn-on” voltage for the bus regulator and brakes. Enter a percentage of the high voltage setting for
the voltage class. For example, on a 400…480V AC drive,

Note: The minimum value for frame 5 and up, 600V AC input drives was changed from 110.5000 to 100.0000
for firmware version 4.002.

(1) The minimum value is 100.0000 for frame 5 and up, 600V AC input drives.

Default:
Min/Max:
Units:

111.0000
110.5000

(1)

/117.8000

%

RW Real

416 Brake

PulseWatts

Limits the power delivered to the external Dynamic Brake (DB) resistor for one second, without exceeding the
rated element temperature. You may change the value of this parameter only if you have selected an external
DB resistor (set bit 1 “Brake Extern” of

Par 414

[Brake/Bus Cnfg]. If this rating is not available from the resistor

vendor, you can approximate it with this equation:

Par 416

[Brake PulseWatts] = 75,000 x Weight, where

Weight equals the weight of resistor wire element in pounds (not the entire weight of the resistor). Another
equation you can use is: Par 416 [Brake PulseWatts] = Time Constant x Brake Watts; where Time Constant
equals the amount of time to reach 63% of its rated temperature while the maximum power is applied, and
Brake Watts is the peak power rating of the resistor.
Note: The maximum value was changed from 1000000.0000 to 1000000000.0000 for firmware version 3.001.

Default:
Min/Max:
Units:

2000.0000
1.0000/1000000000.0000
W

RW Real

Options:

0 = Zero

19 = Bus VltScale

38 = IGBT Rated A

61 = Convt Type

80 = HH1 P/B ID

99 =

HH2 P/B ID

1 = Volt Class

20 = Sml PS Watts

39 = IGBT V Thres

62 = DC Bus Induc

81 = HH1 S/W ID

100 = HH2 S/W ID

2 = Assy Rev

21 = Sml PS Min V

40 = IGBT Slope R

63 = AC Inp Induc

82 = HH1 P/B Rev

101 = HH2 P/B Rev

3 = ASA S/N

22 = Lrg PS Watts

41 = IGBT Sw Engy

64 = Precharg Res

83 = HH1 S/W Rev

102 = HH2 S/W Rev

4 = Manuf Year

23 = Lrg PS Min V

44 = IGBT CS Tres

65 = PrechThrm Tc

84 = HH1 Extr Data

103 = HH2 ExtrData

5 = Manuf Month

24 = Inv Rated Kw

45 = IGBT CS Tc

66 = Mtr NP Units

85 = HH1 VoltIndx

104 = HH2 VoltIndx

6 = Manuf Day

25 = Inv Rated V

46 = Diode V Thrs

67 = Mtr NP Power

86 = HH1 SizeIndx

105 = HH2 SizeIndx

7 = Tst ProcStat

26 = Inv Rated A

47 = Diode SlopeR

68 = Mtr NP Volts

87 = HH1 Option

106 = HH2 Option

8 = Life PwrCycl

27 = Inv 1min Amp

48 = Diode JC Tr

69 = Mtr NP Amps

88 = HH1 HrdPrdct

107 = HH2 HrdPrdct

9 = Life Pwrup

28 = inv 3sec Amp

49 = Diode JC Tc

70 = Mtr NP Freq

89 = HH1 H/W Mdfy

108 = HH2 H/W Mdfy

10 = Life RunTime

29 = SW OverC Amp

50 = GBT Tjmax

71 = Mtr NP RPM

90 = HH1 1V/Amp

109 = HH2 1V/Amp

11 = Kw Accum

30 = DC Bus Cap

51 = HS Max DegC

72 = Mtr IR Vdrop

91 = HH1 2s/Amp

110 = HH2 2s/Amp

12 = Mw Hrs Accum

31 = Min PWM Khz

52 = DB IGBT Amp

73 = Mtr Id Ref

92 = HH1 Scale

111 = HH2 Scale

13 = Inv High Vlt

32 = Max PWM Khz

53 = DB ohms

74 = HH1 Data Rev

93 = HH2 Data Rev

14 = Reserved

33 = Dfl PWM Khz

54 = DB E Jo/degC

75 = HH1 Dev Type

94 = HH2 Dev Type

15 = Fan/Pwr Cntl

34 = PWM Dead us

55 = DB EB C/Watt

76 = HH1 Serial #

95 = HH2 Serial #

16 = Temp Sensor

35 = Drive Frame

56 = DB B Jo/degC

77 = HH1 Test Date

96 = HH2 TestDate

17 = Phs AmpScale

36 = IGBTs per Pk

57 = DB BA C/Watt

78 = HH1 Vcn Code

97 = HH2 Vcn Code

18 = Gnd AmpScale

37 = GBT Rated V

60 = DB Ambt Tmax

79 = HH1 CrsCncID

98 = HH2 CrsCncID

Options

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Bu

s Re

g En

Bu

s Re

f H

ig

h

Brak

e Ex

ter

n

Brak

e E

na

ble

Default

x

x

x

x

x

x

x

x

x

x

x

x

1

1

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True

111

2

×

480 VDC

=

Ч