Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Appendix B

Application Notes

Figure 9 - Sleep-Wake Mode Flow Chart

Is Sleep-Wake

Working?

Have these conditions been met?

Is Required Input Closed?

(Stop, Enable, Run)

Did a Drive

Fault Occur?

Which Required Input

was Chosen?

Meet all Conditions!

Close Input

Reset Fault

Yes

Yes

Stop or Enable

Run

Yes

Yes

Drive Running?

No

Direct

Invert

No

No

No

No

No

No

Issue a Start Command

(HIM, Network or TB)

Open & Close Input

Consult Factory

No

Consult Factory

Which Mode is Selected?

"Invert" or "Direct"

1. [Sleep-Wake Ref] must be set to the analog input that will control

"Start/Stop" functions.

2. [Sleep-Wake Mode] must = "1, Direct" (Enable) or "2, Invert (Enable)."

3. [Sleep Level] must be less than [Wake Level] in Direct mode (or

greater than [Wake Level] in "Invert" mode).

4. [Speed Ref x Sel] must be set to a speed reference source that will

control the drive. If [Sleep-Wake Ref] = [Speed Ref x Sel], the same
analog signal will control start/stop and speed reference.

5. At

least one of the following must be programmed for [Dig Inx Sel]:

"Normal Stop," "Enable," "Start," "Run."

Is Analog Signal

Greater

than or equal to [Wake Level]?

and for time period greater than

or equal to [Wake Time]

Yes

Yes

Is Analog Signal

Less

than or equal to [Wake Level]?

and for time period greater than

or equal to [Wake Time]

Increase Analog Input

Signal and wait for a time

period greater than or
equal to [Wake Time].

Decrease Analog Input

Signal and wait for a time

period greater than or
equal to [Wake Time].

Was a Stop Issued?

or

Power Cycled?