Chapter 1

Drive Start-Up

Prepare for Initial Drive
Start-Up

1.

Confirm that all inputs are connected to the correct terminals and are
secure.

2.

Verify that AC line power at the disconnect device is within the rated value
of the drive.

3.

Verify that control power voltage is correct.

4.

Apply AC power and control voltages to the drive. The drive and HIM
will power up.

If the STS (status) LED is NOT flashing green, refer to Status
Indicators o
n page f

139

or more information.

If any digital input is configured to “Stop - CF” (CF=Clear Faults) or
“Enable”, verify that signals are present or the drive will not start. See

Table 1

on page

17

for other causes of a start inhibit.

5.

When prompted on the HIM, select a display language and press Enter

(

).

The PowerFlex 700S Start-Up screen displays for drives that have not
been previously configured.

ATTENTION: Power must be applied to the drive to perform the following
start-up procedure. Some of the voltages present are at incoming line potential.
To avoid electric shock hazard or damage to equipment, only qualified service
personnel should perform the following procedure. Thoroughly read and
understand the procedure before beginning.

IMPORTANT

When power is first applied, the HIM may require approximately five
seconds until commands are recognized (including the Stop key).

TIP

If the Assisted Start routine has already been accessed and started, you
can return to and continue with the Start-Up routine. See Access the
Start-Up Routine on pa
ge

155

for more information.