Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual

Page 144

Advertising
background image

144

Publication 2711-UM014G-EN-P - September 2008

Chapter 7 Installing the PV300 Terminal

6. Install the self-locking nuts hand tight.

7. Alternately tighten the self-locking nuts until the terminal is held

firmly against the panel

8. Tighten the nuts to a torque of 1.13 Nm (10 lb-in).

Do not over-tighten.

9. Remove the protective installation label covering the top vents

of the terminal.

ATTENTION

Mounting nuts must be tightened to a torque of 1.13 Nm
(10 lb-in) to provide a proper seal and to prevent
potential damage to the terminal. Allen-Bradley
assumes no responsibility for water or chemical damage
to the terminal or other equipment within the enclosure
because of improper installation. A properly installed
terminal has a small gap between the bezel and
enclosure.

ATTENTION

Failure to remove the protective installation label
covering the top vents could result in overheating and
damage to the terminal.

Self-locking nuts
(4 used, 6 provided)

Mounting Studs (2 left, 2 right)

Protective installation label