Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual

Page 174

Advertising
background image

174

Publication 2711-UM014G-EN-P - September 2008

Chapter 11 Installing the PV1400 Terminal

4. Install the 10 mounting clips (three on top, three on bottom, two

on each side).

The ends of the clips slide into slots on the terminal.

5. Tighten the clip mounting screws hand tight.

6. Alternately tighten the mounting clip screws until the terminal is

held firmly against the panel.

7. Tighten mounting screws to a torque of 1.13 Nm (10 lb-in.).

Do not over-tighten.

TIP

The PV1400 terminal has two metal tabs (on bottom
edge) that temporarily lock the terminal against the
panel. These tabs only facilitate installation of the
mounting hardware. The tabs are not designed to
provide permanent mounting.

Install 10 Mounting Clips

= Recommended

Placement of

Mounting Clips

Keypad Version

Touch Screen
Version

ATTENTION

Mounting nuts must be tightened to a torque of 1.13 Nm
(10 lb-in.) to provide a proper seal and to prevent
potential damage to the terminal. Allen-Bradley
assumes no responsibility for water or chemical damage
to the terminal or other equipment within the enclosure
because of improper installation.

Advertising