Mount terminal with mounting studs – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual

Page 175

Advertising
background image

Publication 2711-UM014G-EN-P - September 2008

175

Installing the PV1400 Terminal Chapter 11

Mount Terminal with Mounting Studs

Follow these steps to install the PV1400 terminal in a panel by using
mounting studs.

1. Cut an opening in the panel by using the panel cutout template

shipped with the terminal.

2. Carefully drill 5.56 mm (7/32 in.) holes for studs as indicated.

3. Install the mounting studs (Cat. No. 2711-NP3) using a 7/32-inch

socket on the end of the stud.

4. Turn stud clockwise and tighten to approximately 1.13 Nm

(10 in.-lb).

5. Make sure the sealing gasket is properly positioned on the

terminal.

This gasket forms a compression type seal (NEMA Type 4). Do
not use sealing compounds

.

6. Place the PV1400 terminal in the panel cutout aligning the studs

with the mounting holes.

ATTENTION

Be careful not to damage the sealing gasket when
installing or removing studs. A damaged seal may result
in damage to the PanelView terminal and other panel
components due to a leaking seal.

Spacer

Bezel

Gasket

Mounting Studs
(Qty 18 for Keypad, 12 for Touch)

Self-locking Nuts

Panel or Enclosure

Advertising