Appendix B Messages, Codes and Self-test Numbers

General Terminal
Messages

Error Number

Terminal
Messages

Type

Meaning

Recommended Action

200-206, 300,
318-321, 328,
329, 331, 346,
347, 355, 356,
358, 367, 404,
411, 416, 417,
421-425,
447-449, 457,
459, 700, 1105,
1111, 1113, 1115,
1207-1211,
2002-2009, 2016,
2018, 2021, 2028
and 2029

A fault has
occurred. Error =
X

Minor Fault
or
Terminal Fault

A minor fault was detected that could
impact terminal operation or a
terminal fault was detected.

Press any key to recover from a minor
fault. For terminal faults, contact
technical support with the error code.

208

Write to logic
controller failed

Comm Status

Controller does not accept data from
the terminal. Controller is not
connected.

Check connections (on remote I/O
units). Verify that controller is in run
mode and not busy. Verify that
controller data files are not in use by
other applications.

303

Aborted.

Reminder/File
Transfer Status

The terminal received an abort
command during a file transfer.

Try again.

304

File read access
error

Reminder

Error reading the source file from a
source device.

Try again. If problem continues,
contact technical support.

305

File write access
error

Reminder

Error writing source file.

Try again. If problem continues,
contact technical support.

307

File not
supported

Reminder/File
Transfer Status

File is incompatible with the
terminal’s firmware.

Contact technical support to verify
compatibility. File must be a .PVA file.

308

Timeout

Reminder / File
Transfer Status

The terminal was waiting for the
partner device in a file transfer, but
the terminal timed out before the
data or expected reply was received.

Check cable connections or data
corruption with noise on cable. Verify
that the computer was not reset. Try
again.

309-311

Data corrupted.
Verify file and
retry.

Reminder/File
Transfer Status

The data checksum failed in a file
transfer.

Check electrical and cable
connections. Try the file transfer
again.

312

Unknown device

Reminder / File
Transfer Status

Verify the file type entered. Try again. Destination or source device is invalid

for a read or write application
transfer.

313

File too large

Reminder / File
Transfer Status

Reduce application size. See
Appendix A for terminal
requirements. If copying to a card,
check card space.

File too large to be transferred to the
terminal. In a memory card transfer,
the card does not have enough space.

314

No Card Inserted

Reminder

Install a memory card and try again.

You tried to transfer data to/from a
memory card but there is no card in
the card slot.