Interpret Status Indicators

On PanelView terminals (except PanelView 300 Micro), use the
COMM and Fault Status indicators to isolate operating problems. The
illustration below shows the location of these indicators on some
terminals.

See Chapter 1 for status indicator locations on other terminals.

On PanelView 300 Micro terminals, view the Comm and Fault
indicators in the terminal configuration mode (Communication Setup
selected).

PV550 Back View

PV900 Back View

PV600/PV1000 is similar

COMM
Status
Indicator

Fault
Status
Indicator

Fault Status Indicator

COMM Status Indicator

DF1, DH-485, and DH+ Status Indications

Status
Indicator

This Pattern

Indicates

Comm

(1)

(1)

Comm Status indicator stays on until powerup self-tests are complete.

Solid Fill

Normal operating state (no communication faults).

No Fill

Fault detected.

Make sure controller is run mode

Verify baud settings of terminal and controller

Verify proper terminal to controller connections

Flashing

When power is first applied (momentarily).

Blinking

No communication established. For DF1 terminals,
the Comm indicator flashes until an application is
loaded.

Fault

No Fill

Normal operating state

Solid

Fault detected. Cycle power to the terminal. If the
fault still exists, the terminal requires servicing.

Blinking

Hardware is functioning but no application is
loaded or the current application is corrupt. Reload
the application into the terminal.