Publication 2711-UM014G-EN-P - September 2008

Appendix B Messages, Codes and Self-test Numbers

16417

DHCP/BootP
Enable failed

Communication
Warning

The DHCP/BootP Enable server failed
to allocate an IP address, subnet
mask and gateway address to the
PanelView terminal

Check DHCP/BootP Enable server on
your network.

16418

Invalid IP Address
or Subnet Mask

Communication
Warning

The IP address or the subnet mask of
the PanelView terminal is not valid.

Important: The Gateway Address
cannot be entered at the terminal;
you must configure this address in
the Communication Setup dialog of
PanelBuilder32.

Enter a valid IP address and/or the
subnet mask of the PanelView
terminal on the Communication Setup
screen.

This error occurs if the downloaded
application has DHCP/BootP enabled
and it is then disabled at the
terminal. On a restart, the terminal
will not have the necessary
information (IP Address, Subnet
Mask, Gateway Address) to connect
to the network.

16420

Invalid Gateway
Address

Communication
Warning

The Gateway Address is not valid.

Change the Gateway Address in the
PanelBuilder32 software.

Error Number

Terminal
Messages

Type

Meaning

Recommended Action