Install the pv1400 terminal in a panel – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual

Page 173

Advertising
background image

Publication 2711-UM014G-EN-P - September 2008

173

Installing the PV1400 Terminal Chapter 11

Install the PV1400 Terminal
in a Panel

This section gives procedures for mounting a PV1400 terminal by
using:

mounting clips (10 shipped with terminal, 10 required)

mounting studs (ordered separately, Catalog No. 2711-NP3)

Follow these steps to install the PV1400 terminal in a panel using
clips.

1. Cut an opening in the panel by using the panel cutout template

provided with the terminal and remove any sharp edges or
burrs.

Do not drill the mounting stud holes if you are using clips.

2. Make sure the sealing gasket is properly positioned on the

terminal, particularly around the mounting studs as shown.

This gasket forms a compression type seal. Do not use sealing
compounds.

Although the keypad legend strip can be installed any time, we
recommend that you install them after the terminal is installed.

3. Place the PV1400 terminal in the panel cutout.

The terminal will snap into the panel as the temporary retaining
tabs lock against the panel.

ATTENTION

Disconnect all electrical power from the panel before making the
cutout.

Make sure the area around the panel cutout is clear.

Do not allow metal cuttings to enter any components that may
already be installed in the panel.

Failure to follow this warning may result in personal injury or damage
to the panel components.

Sealing Gasket

Advertising