Messages, Codes and Self-test Numbers Appendix B

16398

The Connection
Originator is
indicating it is in
Program Mode

Comm Warning

The logic controller is offline (in
Program Mode). The COMM Status
indicator on the Configuration Mode
menu is off.

Place the logic controller in run mode
to resume communication.

16399

A fatal CPU fault
occurred

Critical Fault

A fatal CPU fault occurred.

Contact technical support.

16401

The RAM check
failed

Critical Fault

RAM verification failed at startup.

Contact technical support.

16402

The CRC check of
the firmware
failed

Critical Fault

CRC verification failed at startup.

Contact technical support.

16403

OS startup failed

Critical Fault

Operating system failed to start.

Contact technical support.

16404

PV Client Task
Fault

Critical Fault

Internal error has occurred.

Contact technical support.

16405

Invalid preset
information
received from
motherboard.

Critical Fault

Internal error has occurred.

Contact technical support.

16406, 16407

Connection with
Addr or scan rate
invalid or no
connection being
attempted.

Critical Fault

Internal error has occurred.

Contact technical support.

16408

No buffers
available for read
operation

Critical Fault

Internal error has occurred.

Contact technical support.

16409

DC couldn’t send
out the write
request in time.

Critical Fault

Too many write operations are
occurring.

Contact technical support.

16410

Too many clients
attempted to
connect to server

Critical Fault

Internal error has occurred.

Contact technical support.

16411

XS-WD creation
error

Critical Fault

Internal error has occurred.

Contact technical support.

16412

XS-WD start
error

Critical Fault

Internal error has occurred.

Contact technical support.

16413

ENet addr is not
valid

Communication
Warning

The EtherNet address for a device on
the EtherNet/IP network is invalid.

Contact technical support.

16414

Duplicate IP
address detected

Critical Fault

The PanelView has the same IP
address as another device on the
EtherNet/IP network.

Change the IP address of the
PanelView (on the Communication
Setup screen) so that is unique on the
network.

16415

Unknown error
detected

Communication
Warning

An operating system message has
occurred.

Contact technical support.

16416

No network link

Critical Fault

Communication has not been
established with network.

Check Ethernet cable.

Error Number

Terminal
Messages

Type

Meaning

Recommended Action