RS-232/DF1 Port Connector

The DF1 port on the PanelView terminal is a 9-pin, male, RS-232
connector. The table below shows the pinout descriptions for this port
and how these pins map to the DF1 ports on the controllers.

The maximum cable length for DF1/full duplex communication is
15.24 m (50 ft).

Connecting to a MicroLogix 1000 Controller

The following shows a point-to-point connection between the RS-232
(DF1) port of the PanelView terminal and a MicroLogix 1000
controller.

The 1761-NET-AIC module is used only with the MicroLogix controller
and eliminates grounding level differences between the controller and
PanelView terminal.

DF1 Port
9-pin DCE

SLC
9-pin

PLC
25-pin

MicroLogix/
DNI 8-pin DIN

1

2

2

3

4

3

3

2

7

4

4

20

5

5

7

2

6

6

6

7

7

4

8

8

5

9

RXD

TXD

DTR

COM

DSR

RTS

CTS

MicroLogix 1000

PanelView

1761-CBL-HM02

2711-NC13, -NC14 Cable

DF1 Port

DF1 Port

1761-NET-AIC

AIC+

MicroLogix 1000, 1200, 1500LSP

PanelView

Cables:

DF1 Port

2711-NC21
2711-NC22

Use a direct connection when both the PanelView and MicroLogix
use the same power supply. Otherwise, use the AIC for electrical
isolation as shown to the right.