Enclosures, Required tools, Enclosures required tools – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual
Page 162

162
Publication 2711-UM014G-EN-P - September 2008
Chapter 10 Installing the PV900/1000 Terminals
The PV900/PV1000 terminals have an operating temperature code of
T4 (maximum operating temperature of 135
°
C or 275 °F). Do not
install the terminals in environments where atmospheric gases have
ignition temperatures less than 135 °C (275 °F).
Enclosures
The PV900/PV1000 terminal must be mounted in an environment that
provides IEC-1131-2 Pollution degree 2 protection.
Mount the terminal in a panel or enclosure to protect the internal
circuitry. The terminal meets NEMA Type 12/13 and 4X (indoor use)
ratings only when mounted in a panel or enclosure with the
equivalent rating.
Allow enough space within the enclosure for adequate ventilation.
Consider heat produced by other devices in the enclosure. The
ambient temperature around the terminals must be between 0…55 °C
(32…131 °F).
Required Tools
Other than the tools required to make the panel cutout, the tools
required for installation are:
•
small slotted screwdriver
•
torque wrench (lb-in) with slotted or phillips head driver