Publication 2711-UM014G-EN-P - September 2008

61

Applying Power and Resetting Terminal Chapter 2

Connect AC Power

Below are AC electrical ratings for the PanelView terminals. The
PV550/PV600 touch screen only terminal is available only with DC
power, not AC power.

The PanelView terminals are IEC 1131-2 Equipment Class I devices

and require you to connect the GND (Ground) or

(Protective

Earth) terminal to an earth conductor.

Follow these steps to connect power to the AC versions of the
PanelView.

1. Secure AC power wires to the L1 and L2N terminal block screws.

2. Secure the Earth Ground/Protective Earth wire to the GND or

the

screw on the terminal block.

3. Apply power to the terminal.

Terminal Type

Supply Voltage

Power Consumption,
Max

PV550

85…264V AC, 47…63 Hz

45 VA

PV600

85…264V AC, 43…63 Hz

60 VA

PV900M/PV900C

85…264V AC, 47…63 Hz

110 VA

PV1000G/PV1000C

85…264V AC, 47…63 Hz

55 VA

PV1400

85…264V AC, 43…63 Hz

200 VA

ATTENTION

Do not apply power to the PanelView terminal until all wiring
connections have been made. Failure to do so may result in
electrical shock.

IMPORTANT

The PanelView terminals are designed for safe use when
installed in a NEMA Type 12, 13, 4X (indoor use only), IP54 or
IP65 rated enclosure.

ATTENTION

Improper wiring of the power terminals may result in
voltage at the communication connector shells.

See the appropriate wiring diagram on page 62.