Appendix B Messages, Codes and Self-test Numbers
If a test fails, the terminal displays:
ERROR! FEHLER! ERREUR! ERRORE!
The following test numbers appear only if a problem occurs.
The table below shows fault conditions that may occur during
powerup.
25
Firmware not compatible with boot code
26
Firmware not compatible with hardware
30
Watchdog test
31
Stuck key test
32
Real time clock test
33
LCD RAM failed
34
Performed CRC extended firmware check
TIP
You may not see all of these test numbers during a powerup.
Test Number
Indicates
40
No executable code to run after boot
50
Wrong memory card format
60
CPU could not execute code
Fault Indicator
Indicates
Solid Red
Static RAM Test failed. Contact technical support.
Blinking Red
(6 times per second)
Checksum test on boot code failed. Contact technical
support.
Blinking Red
(5 seconds on/5 seconds
off)
Boot code is incorrect for terminal type (touch screen or
keypad). Contact technical support.
Test Number
Indicates