Publication 2711-UM014G-EN-P - September 2008

263

Messages, Codes and Self-test Numbers Appendix B

These messages appear on the terminal screen as DC Error=xx. If you
get an alert number that is not listed here, contact technical support.

EtherNet/IP Codes

These messages appear on the terminal screen as DC Error=xx. If you
get an alert number that is not listed here, contact technical support.

ControlNet
Alert Codes

Alert Type

Indicates:

Recommended Action

9000

Critical fault

Interface startup failed.

Contact technical support.

9003

Critical fault

CIP S/N is not valid.

Contact technical support.

9004

Critical fault

Out of buffers.

Contact technical support.

9010

Critical fault

Invalid target node, target node
is the same as the PanelView, or
larger than the UMAX.

Check node address of all devices on the network
including the PanelView terminal.

9012

Communication
Warning

ControlNet object received a
reset request.

Contact technical support.

9014

Critical fault

A fatal CPU fault occurred.

Contact technical support.

9015

Critical fault

A ControlNet hardware fault
occurred.

Contact technical support.

9016

Critical fault

RAM verification failed at
startup.

Contact technical support.

9017

Critical fault

CRC verification failed at
startup.

Contact technical support.

9018

Critical fault

A critical internal error occurred. Contact technical support.

9019

Critical fault

An internal fault occurred.

Reset terminal, if problem occurs again, contact
technical support.

9020

Critical fault

An internal fault occurred.

Reset terminal. If problem occurs again, reload
application. If problem persists, contact technical
support.