Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual

Page 264

Advertising
background image

264

Publication 2711-UM014G-EN-P - September 2008

Appendix B Messages, Codes and Self-test Numbers

Error Number

Terminal
Messages

Type

Meaning

Recommended Action

xx,xx,xx

Number depends
on hardware fault
detected.

Communication
Interface Fault

Critical Fault

A hardware problem was detected
during power-up. If you ignore
message and display the EtherNet/IP
Communication Screen, the Comm
Status displays “Comms hardware
fault:” without an error number. The
FW revision, serial number and
EtherNet/IP address fields are
displayed.

Contact technical support to have unit
repaired.

770

Buffer overflow

Comm Status

Internal error occurred.

Contact technical support.

771

Buffer underflow

Comm Status

Internal error occurred.

Contact technical support.

1799 Heap

partition

empty

Comm Status

Internal error occurred.

Contact technical support.

16387

Comms not
started yet...

Comm Status

The PanelView has not connected to
the network.

Check IP configuration (on the
Communication Setup screen) and
wait for PanelView to connect to the
network.

16388

CIP S/N is not
valid

Critical fault.

DC incorrectly configured.

Contact technical support.

16389

Out of buffers

Critical fault.

No buffers are available for read or
write operations.

Contact technical support.

16390

An initial write
failed

Comm Warning

Write to Logic Controller on Startup
was configured and on powerup, the
PanelView could not write initial
values to a node's data table address.

or

Write to Logic Controller on Startup
was not configured and the
PanelView was unable to write a
controller. Note: The error is only
displayed on the first write attempt.

Check/define data table address in
the controller.

Check communication connections
and node configuration in the
application.

16391

PV write failed

Comm Warning

PanelView is communicating with the
controller. The data table address
does not exist.

Check/define data table address in
the controller.

16392

PV write timeout

Comm Warning

PanelView is not communicating with
the logic controller.

Check connections and node
configuration in the application.

16393

PV read fail

Comm Warning

PanelView is communicating with the
controller. The data table address
does not exist.

Check/define data table address in
the controller.

16394

PV read timeout

Comm Warning

PanelView is not communicating with
the controller.

Check/define data table address in
the controller.

16397

CN object
received a reset
request

Comm Warning

An Ethernet object received a reset
request from a device on the network.

The PanelView does not support
network resets.