Publication 2711-UM014G-EN-P - September 2008

Appendix B Messages, Codes and Self-test Numbers

Remote I/O Terminal Messages

EtherNet/IP Messages

For a description of EtherNet/IP terminal codes, see page 263.

Error Number

Terminal
Messages

Type

Meaning

Recommended Action

661

Timeout - No
Block Transfer
Writes

Comm Status

The PLC is communicating with the
terminal, but the PanelView is not
receiving BTW requests required by
the application.

Check ladder logic for missing BTW
instructions (instructions are not
enabled) or addressing errors. Check
for logic controller errors.

662

Timeout - No
Block Transfer
Reads

Comm Status

The PLC is communicating with the
terminal, but the PanelView is not
receiving BTR requests required by
the application.

Check ladder logic for missing BTR
instructions (instructions are not
enabled) or addressing errors. Check
for logic controller errors.

663

Timeout - No
Block Transfer
Requests

Comm Status

The PLC is communicating with the
terminal, but the PanelView is not
receiving BTR or BTW requests
required by the application.

Check ladder logic for missing BTR or
BTW instructions (instructions are not
enabled) or addressing errors. Check
for logic controller errors.

664

PLC in program
mode

Comm Status

The PLC is offline (in Program Mode).
The COMM Status indicator on the
Configuration Mode menu is off.

Place the PLC in run mode to resume
communication.

665

No PLC
communication

Comm Status

The PLC is not communicating.
Possible causes are disconnected
cable, no power to PLC, incorrect
baud rate or rack settings for PLC
configuration. COMM Status
indicator is off.

Check for pulled cables and PLC
power. Check baud rate settings and
rack configurations.

Check wiring of connector.

Communication resumes when
problem is corrected.

666

Invalid Rack
Configuration

Comm Status

No communication can occur because
of an invalid rack configuration.

Correct the RIO rack configuration.

667

Remote I/O
Hardware Failed

Comm Status

During startup, the terminal detected
a missing, corrupt or nonfunctional
remote I/O card. The terminal will run
but not communicate.

Contact technical support and provide
specific message.