Chapter 3 Configuring the Terminal

New Node Address

Opens the numeric entry scratchpad. Enter the node address (01…99
decimal) of the terminal and press the Enter

key. On touch screen

terminals, press the

key on the scratchpad. The initial default is 3.

The change takes effect after the terminal is reset. If you enter a value
greater than the UMAX node address, the terminal will not go online
with the network.

Active Node Address (read only)

Displays the current address of the PanelView terminal.

Underscan Delay

Opens the numeric entry scratchpad so you can change the Interscan
Delay. Enter the delay (100…1000 milliseconds in multiples of 100)
and press the Enter key. On touch screen terminals, press the

key

on the scratchpad. The initial default is 100. A change takes effect
immediately.

FW Revision (read only)

Shows the revision # of the firmware in the ControlNet terminal.

Serial Number (read only)

Displays a unique, 32-bit serial number for the PanelView terminal.

Comms Status

Displays the current status of the communication card. Connected
appears when the PanelView is connected to the network and
operating properly.

Channel Status

Displays a value indicating the current status of channel A and B. The
definition of each status condition follows the table. If multiple status
conditions apply, the highest priority condition is displayed.

Displayed
Value

Status
AB

Displayed
Value

Status
AB

Displayed
Value

Status
AB

Displayed
Value

Status
AB

119

7 7

87

7 5

55

7 3

23

7 1

118

6 7

86

6 5

54

6 3

22

6 1

117

5 7

85

5 5

53

5 3

21

5 1

116

4 7

84

4 5

52

4 3

20

4 1