Dh-485 terminal messages – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual

Page 254

Advertising
background image

254

Publication 2711-UM014G-EN-P - September 2008

Appendix B Messages, Codes and Self-test Numbers

DH-485 Terminal Messages

2011

Retained memory
lost. Presets
were loaded.

Reminder

The battery backed memory was
invalid during startup. The system
defaulted to preset values instead of
the last states.

No action necessary. Terminal reverts
to defaults.

2012

Application file:
Too many
retained memory
devices

Terminal Fault

The battery-backed RAM is too full to
hold all devices requiring presets.

Reduce the number of control objects.
Use global objects.

2014

Hardware
configuration is
corrupted

Terminal Fault

The terminal hardware configuration
is corrupt.

Contact technical support.

2030, 2031

Hardware and
firmware do not
match

Terminal Fault

A mismatch exists between the
terminal firmware and the terminal
hardware.

Verify that the series and revision
markings on the back of the terminal
are compatible with the firmware.

Error Number

Terminal
Messages

Type

Meaning

Recommended Action

Error Number

Terminal
Messages

Type

Meaning

Recommended Action

612

No active node(s)
found on network

Comm Status

Tag or address does not exist or is the
wrong data type.

Check tag address.
Check for data type mismatch.

613

Required network
node(s) not found

Comm Status

Tag or address does not exist or is the
wrong data type.

Check tag address.
Check for data type mismatch.

615

Duplicate node
address

Comm Status

More than one node was assigned
the same address.

Verify all device nodes.

616

Data errors on
the link

Comm Status

Corrupt data packets were detected
on DH-485 network.

Verify controller addressing and baud
rate settings. Check for loose or
reversed wiring.