Making DH+ Connections

Use the Belden 9463 twin axial cable (1770-CD) to connect a DH+
PanelView terminal to the DH+ link.

You can connect a DH+ link in 2 ways.

trunk line/drop line - from the drop line to the connector
screw terminals on the DH+ connectors of the processor

daisy chain - to the connector screw terminals on the DH+
connectors on the processor

Follow these guidelines when installing DH+ communication links.

do not exceed these cable lengths:

trunk line-cable length: 3,048 m (10,000 ft)

drop-cable length: 30.4 m (100 ft)

do not connect more than 64 stations on a single DH+ link

Clear 1

Shield SH

Blue 2

Blue 2

Shield SH

Clear 1

1770-CD (Belden

Cable)

Blue 2

Shield SH

Clear 1

PLC 5/11, -5/20, 5/26 Processor

PLC-5/30, -5/40, -5/46, -5/40L, - 5/60, -5/60C

-5/60L, -5/80, 5/80C, -5/86 Processor

PanelView 1000 DH+ Terminal

PanelView 550 DH+ Terminal

82 or 150 Ohm Resistor

82 or 150 Ohm Resistor

Clear = 1

Shield

Blue = 2