Configuring the Terminal Chapter 3

DH+ Communication

The DH+ screen lets you display or modify communication settings
for the DH+ version of the PanelView terminals.

Node

Opens the numeric entry scratchpad. Enter the node address (0…77
octal) of the terminal on the DH+ link and press the Enter

key. (On

touch screen terminals, press the Enter key on the scratchpad). A
node change takes effect immediately.

Baud

Steps through the communication rates with each key press: 57.6K
(default), 115.2K, and 230.4K. The selected rate takes effect
immediately. The maximum cable length is restricted at higher
communication rates.

Comm Status Indicator

solid fill - normal operating state

blinking - no communication established

no fill - hardware failure

Fault Status Indicator

no fill - normal operating state

blinking - hardware is functioning but an application is not
loaded or the current application is corrupted.

solid fill - hardware failure

IMPORTANT

Settings downloaded with a DH+ application take priority over
terminal settings and take effect immediately after the
download.

DH+