Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual

Page 168

Advertising
background image

168

Publication 2711-UM014G-EN-P - September 2008

Chapter 10 Installing the PV900/1000 Terminals

4. Install the 6 mounting clips (2 on top, 2 on bottom, 1 on each

side).

The ends of the clips slide into the slots on the terminal.

5. Tighten the clip mounting screws by hand until the gasket seal

contacts the mounting surface uniformly.

6. Alternately tighten the mounting clip screws to a torque of

1.13 Nm (10 lb-in).

Do not over-tighten.

7. Remove the two protective labels covering the top vents of the

terminal.

ATTENTION

Mounting nuts must be tightened to a torque of 1.13 Nm
(10 lb-in) to provide a proper seal and to prevent
potential damage to the terminal. Allen-Bradley
assumes no responsibility for water or chemical damage
to the terminal or other equipment within the enclosure
because of improper installation. A properly installed
terminal has a small gap between the bezel and
enclosure.

ATTENTION

Failure to remove the protective installation label
covering the top vents could result in overheating and
damage to the terminal.

Install six mounting clips:
Top - left and right slots
Bottom - left and right slots
Sides - left and right

Protective installation labels

Advertising