Publication 2711-UM014G-EN-P - September 2008

Chapter 12 Terminal Connections

Connecting to an SLC, CompactLogix, MicroLogix Controller
(Point-to-point)

This section shows how to connect a CompactLogix, MicroLogix
1500LRP, or SLC controller (SLC 5/03, SLC 5/04, or SLC 5/05) to the
RS-232 PanelView terminal for point-to-point (DH-485)
communication. On terminals with two ports, use the RS-232
communication port.

For the SLC, CompactLogix or MicroLogix 1500LRP controller, use one
of these cables:

5 m (16.4 ft) Cat. No. 2711-NC13

10 m (32.7 ft) Cat. No. 2711-NC14

3 m (10 ft) Cat. No. 2706-NC13

For the MicroLogix 1000, MicroLogix 1200, or MicroLogix 1500LSP
controller, use one of these cables:

5 m (16.4 ft) Cat. No. 2711-NC21

15 m (49 ft) Cat. No. 2711-NC22

To PanelView Terminal 9-pin,

Male, D-Shell Connector

1
2
3
4
5
6
7
8
9

1
2
3
4
5
6
7
8
9

Pin #

Pin #

To SLC 5/03, 5/04, 5/05, Compact

Logix or MicroLogix 1500LRP Channel
0 Port 9-pin, Male, D-Shell Connector

Required

Data Out (TXD)

Data In (RXD)

Signal Common

Data Out (TXD)

Data In (RXD)

Signal Common

Cable, Cat. No. 2711-NC13
Cable, Cat. No. 2711-NC14
Cable, Cat. No. 2706-NC13

PanelView 1000 Terminal

SLC 5/03, 5/04, 5/05

1

5

9

6

6

9

5

1

CompactLogix

MicroLogix 1500LRP

IMPORTANT

You must configure the Channel 0 Port of the SLC 5/03,
SLC 5/04, SLC 5/05 controller for DH-485 communication using
the Resolutes 500 or AI500 software.

MicroLogix 1000, 1200, 1500LSP

PanelView 1000 Terminal

Cable, Cat. No. 2711-NC21
Cable, Cat. No. 2711-NC22

(null modem not required)