Publication 2711-UM014G-EN-P - September 2008

69

Applying Power and Resetting Terminal Chapter 2

Press this function key on

To set this RIO
parameter

Description

Options

550/600

900/1000/1400

F1

Rack #

Rack address of terminal on RIO network.

On PV550/600: Press

to open the

scratchpad. Enter the rack address and
press

again.

On PV900/PV1000/PV1400: Press F1 to
set the rack #, then use the up and down
arrow keys to select an address.

0…76

F1

F2

Rack Size

Rack size of terminal. Each key press
displays a different size. The terminal
occupies a single rack.

1/4, 1/2, 3/4, Full

F2

F3

Starting Module Group Starting module group number of the

terminal in the assigned rack. Each key
press displays a different module group.

0,1 2,3 4,5 6,7

F3

F4

Pass-through Enabled

Enables or Disables Pass-through, which
lets you transfer applications between a
computer on a DH+ link and a terminal on
a remote I/O link. A PLC-5 controller
passes data between the networks.

Yes or No

F4

F5

Last Chassis

Specifies whether the terminal occupies
the last module group in the assigned
rack (applies only to PLC2 controllers).

Yes or No

F5

Block Transfer Timeout Timeout value for block transfers. Each

key press toggles a value.

0…60 seconds
(0 is the default)

F6

F6

Baud Rate

Communication rate at which the
terminal will communicate on the RIO
network.

BaudMax. Cable Length
57.6K 10,000 ft
115.2K 5,000 ft
230.4K 2,500 ft