Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual

Page 76

Advertising
background image

76

Publication 2711-UM014G-EN-P - September 2008

Chapter 3 Configuring the Terminal

Max Node

Opens the numeric entry scratchpad. Enter the highest node number
on the network (up to 31) and press the Enter

key. (On touch

screen terminals, press the

key on the scratchpad). A change to the

maximum node address takes effect immediately.

Node

Opens the numeric entry scratchpad. Enter the node address of the
terminal (0…31) and press the Enter

key. (On touch screen

terminals, press the ø key on the scratchpad). If you enter a value
greater than the maximum node address, the value is accepted and
the maximum node address is updated. A node address change takes
effect immediately.

Baud

Steps through the communication rates with each key press: 1200,
2400, 9600, and 19200. The selected communication rate takes effect
immediately.

Comm Status Indicator

solid fill - normal operating state

blinking - no communication established

no fill - hardware failure

Fault Status Indicator

no fill - normal operating state

blinking - hardware is functioning but an application is not
loaded or the current application is corrupted.

solid fill - hardware failure

DH-485

Max Node:

Node:

F1

F2

Comm

F16

EXIT

LED

Fault

LED

31

2

Baud:

F3

19200

Advertising