Chapter 3 Configuring the Terminal
Max Node
Opens the numeric entry scratchpad. Enter the highest node number
on the network (up to 31) and press the Enter
↵
key. (On touch
screen terminals, press the
↵
key on the scratchpad). A change to the
maximum node address takes effect immediately.
Node
Opens the numeric entry scratchpad. Enter the node address of the
terminal (0…31) and press the Enter
↵
key. (On touch screen
terminals, press the ø key on the scratchpad). If you enter a value
greater than the maximum node address, the value is accepted and
the maximum node address is updated. A node address change takes
effect immediately.
Baud
Steps through the communication rates with each key press: 1200,
2400, 9600, and 19200. The selected communication rate takes effect
immediately.
Comm Status Indicator
•
solid fill - normal operating state
•
blinking - no communication established
•
no fill - hardware failure
Fault Status Indicator
•
no fill - normal operating state
•
blinking - hardware is functioning but an application is not
loaded or the current application is corrupted.
•
solid fill - hardware failure