Applying Power and Resetting Terminal Chapter 2

Connect DC Power

The L1 versions (Cat. No. 2711-K5 A5 A18...32V1L1, 2711-T9C1L1) of
the PV300, PV300 Micro, PV550, PV600, PV900, and PV1000 terminals
connect to a 24V DC power source.

The table below shows the electrical ratings for the DC versions of the
terminals. Electronic circuitry and an internal fuse protect the
terminals from reverse polarity and over-voltage conditions.

Terminal Type

Supply Voltage
(24V DC nominal)

Power Consumption, Max

PV300 Micro

11...30V DC

2.5 W (0.105 A @ 24V DC)

PV300

18...32V DC

6 W (0.25 A @ 24V DC)

PV550

18...30V DC

18 W (0.75 A @ 24V DC)

PV550 (touch only)

18...32V DC

18 W (0.75 A @ 24V DC)

PV600

18...32V DC

24 W (1.0 A @ 24V DC)

PV600 (touch only)

18...32V DC

24 W (1.0 A @ 24V DC)

PV900M

18...30V DC

58 W (2.5 A @ 24V DC)

PV900C

18...32V DC

50 W (2.1 A @ 24V DC)

PV1000G

18...32V DC

24 W (1.0 A @ 24V DC)

PV1000C

18...32V DC

24 W (1.0 A @ 24V DC)

ATTENTION

Do not connect a DC rated PanelView terminal to an AC power
source. Connecting to an AC power source may damage the
terminal.

IMPORTANT

The PanelView terminals are designed for use when installed in
a NEMA Type 12, 13, NEMA 4X (indoor use only), IP54 or IP65
rated enclosure.

ATTENTION

Do not power PanelView terminals from the I/O power on a
controller or from DeviceNet network power. If you try to do
this, the PanelView will not power up and the DeviceNet or
controller power supply may be over-stressed.

ATTENTION

Use only a safety extra-low voltage (SELV) power supply as a
source for the PanelView 300 Micro, PanelView 300 or 550
touch screen terminal. A SELV power supply does not exceed
42.4V DC.