Making Remote I/O Connections

To connect a PanelView terminal to a remote I/O scanner, use cable
Catalog No. 1770-CD (equivalent to Belden 9463). The maximum
cable length (link distance) is determined by the communication rate.

2,800 m (10,000 ft) for 57.6K baud

1,400 m (5,000 ft) for 115.2K baud

700 m (2,500 ft) for 230.4K baud

See Programmable Controller Wiring and Grounding Guidelines,
publication 1770-4.1. The user manual for the I/O scanner module
also provides cabling information.

TIP

The polarity of the remote I/O connector on the PanelView
terminal is reversed from the PLC Scanner connector. However,
the polarity is the same as the scanner card connection to the
SLC controller.

TIP

If the terminal is the last device on the link, connect a 1/2 watt
terminating resistor across terminals 1 and 2. The value of the
resistor depends on the remote I/O communication rate:

for 57.6 kilobaud and 115.2 kilobaud, use a 150-ohm resistor

for 230 kilobaud, use an 82-ohm resistor

Remote I/O Port 3-pin Terminal Block
Connector

Clear = 2

Blue = 1

Shield

Cable (Cat. No. 1770-CD)

Connector (One provided with
terminal)

To PLC or Scanner
Remote I/O Port

PanelView 1000 Keypad

PanelView 550 Keypad