Messages, Codes and Self-test Numbers Appendix B

ControlNet Terminal Messages

See Terminal Codes for messages below

Error Number

Terminal
Messages

Type

Meaning

Recommended Action

634

PanelView offline Comm Warning

PanelView is offline.

Check connections

634

Write fail.

Comm Warning

PanelView is communicating with the
controller. The data table address
does not exist.

Check / define data table address in
the controller.

634

Write timeout.

Comm Warning

PanelView is not communicating with
the logic controller.

Check connections and node
configuration in the application.

634

Read fail.

Comm Warning

PanelView is communicating with the
controller. The data table address
does not exist.

Check/define data table address in
the controller.

634

Read timeout.

Comm Warning

PanelView is not communicating with
the controller.

Check/define data table address in
the controller.

636

Initial write
failed.

Reminder

Write to Logic Controller on Startup
was configured and on powerup, the
PanelView could not write initial
values to a node's data table address.

or

Write to Logic Controller on Startup
was not configured and the
PanelView was unable to write a
controller. Note: The error is only
displayed on the first write attempt.

Check/define data table address in
the controller.

Check communication connections
and node configuration in the
application.