Applying Power and Resetting Terminal Chapter 2

Follow these steps to connect power to the dc versions of the
PanelView.

1. Secure the DC power wires to the terminal block screws.

2. Secure the Functional Earth Ground (FE) wire to the correct

terminal block screw.

The dc negative and Functional Earth Ground wires are
internally connected in the PanelView 300 Micro terminal.

3. Apply 24V DC power to the terminal.

+

-

Remove Terminal Block
Insert tip of screw driver
here.

Press terminal block
base in first with
block leaning outward

Push top back to
vertical position
to lock-in.

Use #16 to #22 AWG Solid Wire or
#18 to #22 AWG Stranded Wire.

PanelView 550/600 Terminal

PanelView 300 Terminal

PanelView 900/1000 Terminal

Power Terminal

Block (fixed)

Power Terminal

Block (fixed)

Earth Ground
DC Negative
DC Positive

PanelView 300 Micro Terminal

Install Terminal Block

DC Positive

DC Negative

Functional Earth Ground

+

-

Note: In the PanelView 300, the Earth Ground
and DC Negative wires are internally connected.