Applying Power and Resetting Terminal Chapter 2
Follow these steps to connect power to the dc versions of the
PanelView.
1. Secure the DC power wires to the terminal block screws.
2. Secure the Functional Earth Ground (FE) wire to the correct
terminal block screw.
The dc negative and Functional Earth Ground wires are
internally connected in the PanelView 300 Micro terminal.
3. Apply 24V DC power to the terminal.
+
-
Remove Terminal Block
Insert tip of screw driver
here.
Press terminal block
base in first with
block leaning outward
Push top back to
vertical position
to lock-in.
Use #16 to #22 AWG Solid Wire or
#18 to #22 AWG Stranded Wire.
PanelView 550/600 Terminal
PanelView 300 Terminal
PanelView 900/1000 Terminal
Power Terminal
Block (fixed)
Power Terminal
Block (fixed)
Earth Ground
DC Negative
DC Positive
PanelView 300 Micro Terminal
Install Terminal Block
DC Positive
DC Negative
Functional Earth Ground
+
-
Note: In the PanelView 300, the Earth Ground
and DC Negative wires are internally connected.