TECHNICAL NOTE

<SLAVEOFF> Input and Output Register Map


Output Registers
The following registers are used as outputs from the function block. They can be
monitored by the LadderWorks program to check the execution of the function.

Output Type

Description

RUNNING

Bit

Goes high while offset value is being updated in RDA
and there are no errors

DONE

Bit

Goes high when offset change is complete in RDA

ERROR

Bit

Goes high if any block errors occur



Input Registers
The following registers are used as inputs to the function block. They select the options
and define the parameters that the user needs to make the Home function work as
necessary.

INPUT

TYPE

Content

Range of setting and state

EXECUTE

Bit

Block enable – Block cannot
execute unless this is TRUE.

Rising edge initiates block
TRUE – Block enable
FALSE – Block disable, set all
outputs to zero and off

DST-TIME

Bit

Selects master position [count] or
time [ms] for offset duration.

TRUE – Master position is used for
duration
FALSE – Time is used for duration

M-S-PAIR

Word

Defines which Master-Slave pair
is updated in RDA

1 to 10 value. Any other value will
cause the error output to go on

DURATION

Long

Depends on DST-TIME setting.
Either time or distance master
must travel to complete change in
offset.

Distance: 2147483648~
2147483647 [count]
Time: 0-2147483647 [ms]

OFFSET

Long

Total value offset in RDA will
change.

-2147483648~2147483647

DATA23W

Address Address of the first working

register.

Twenty-three words of register
space are used by this function.

<SLAVEOFF> Block Fault Condition:

The following table outlines several situations that may cause an error, and will turn on
the blocks “Error” output bit. The block “Error” output will cleared if the EXECUTE bit
goes low.

Internal Fault Bit

Cause

Note

inrng1
AB00000E

MSTRSLV value
out of range

Inrng1 must be high if execute is on or an
error will occur. MSTRSLV must have a
value from one to ten for this bit to be on.
Sets RDA Error ID (MW30181) bit 3.

File: MP2000_IndividualFunctionDocument_RevC 101/168
Doc Number: eng.MCD.05.101

11/17/2005