Asciiout> block fault conditions, Asciiout> working register – Yaskawa MP2000 User Manual
Page 162
 
TECHNICAL NOTE
<ASCIIOUT> Block Fault Conditions:
The following table outlines several situations that may cause an error, and will turn on 
the blocks “Error” output bit. The block “Error” output will OFF if the EXECUTE bit goes 
low. 
Internal Fault Bit
Cause
Note
inRng1 
AB000003 
Improper cir 
number. Out of 
range. 
On the initial pass of the block the bit must 
be high or an error will occur. Sets RDA 
Error ID (MW3**81) bit 3 on if error state 
exists. 
inRng2 
AB000004 
Improper slave 
address 
On the initial pass of the block the bit must 
be high or an error will occur. Sets RDA 
Error ID (MW3**81) bit 3 on if error state 
exists. 
snderr 
AB00001F 
MSG-SND has an 
error. 
The MSG-SND internal function has an 
error. Refer to ERROR-ID output for 
value. 
81= function code error 
82= address set error 
83= data size error 
84= line number set error 
85= channel number set error 
86= station address error 
88= transmission part error 
89= device selection error 
 
<ASCIIOUT> Working Register 
This table outlines the data in the Twenty-three registers used by the function block. 
There is not usually any need for the user to access any of these bits directly. The 
MSG-SND type registers can be further understood by referencing the MSG-SND 
function block in the on line help. 
Register No
Type
Name
Description
AW00000
Bit 0
IN
execute
EXECUTE input (XB000000)
Bit 1
Working
crlf
If True, a carriage return and Line feed are inserted at the end 
of the table. 
Bit 2
Working
oddnum
Reserved
Bit 3
OUT
inRng1
Verifies that CIR-NUM input (XW00003) is in range
Bit 4
OUT
inRng2
Verifies that SLAVE input (XW00004) is in range
Bit 7
OUT
running
Directly controls YB000000 (RUNNING Output)
Bit 8
OUT
done
Directly controls YB000001 (COMPLETE Output)
Bit 9
OUT
error
Directly controls YB000002 (ERROR Output)
Bit A
Working
oneshotA
Reserved
Bit B
Working
firstPass
One shot on rising edge of EXECUTE input to initialize RDA & 
sets parameters in the message send function 
File: MP2000_IndividualFunctionDocument_RevC 162/168 
Doc Number: eng.MCD.05.101 
11/17/2005