<CHNGDYN> Block Fault Condition

The following table outlines several situations that may cause an error, and will turn on
the blocks “Error” output bit. The block “Error” output will cleared if the EXECUTE bit
goes low, but the Error ID (MW3**81 and MW3**82) will remain in the RDA. To reset
the Error ID, use the Alarm Reset Function Block.
Note that each axis has its own Error ID stored in its RDA axis section, offset by 200 for
each axis. Example: Axis#1 stores to MW30181, Axis #2 stores to MW30381, etc.

Internal Fault Bit

Cause

Note

JerkOut
AB000001

S-curve value is
not within
acceptable
range.

Bit must be on or error will occur. Sets
RDA Error ID (MW3**81) bit 3 on if
error state exists.

AccelOut
AB000002

Acceleration
value is not
within acceptable
range.

Bit must be on or error will occur. Sets
RDA Error ID (MW3**81) bit 3 on if
error state exists.

DecelOut
AB000003

Deceleration
value is not
within acceptable
range

Bit must be on or error will occur. Sets
RDA Error ID (MW3**81) bit 3 on if
error state exists.

VelOut
AB000004

Speed value is
not within
acceptable
range.

Bit must be on or error will occur. Sets
RDA Error ID (MW3**81) bit 3 on if
error state exists.

axisInErr
AB000005

The axis number
entered on the
input is not an
acceptable value

The function block can only control 1
to 16 axis. Any value greater or
smaller then this will cause an error.
This does not set the RDA Error ID.

<CHNGDYN> Working Register

This table outlines the data of six registers used in the function block. The user is, and
there is not a necessity and either is usually no what directly accessed any of these bits.

Register No

TYPE

Name

Content

AW00000

Bit 0

IN

execute

Execute

input (XB000000)

Bit 1

Working

jerkOut

Verifies that the SCURVE input (XW00001) is in range.

Bit 2

Working

accelOut

Verifies that the ACCEL input (XW00002) is in range.

Bit 3

Working

decelOut

Verifies that the DECEL input (XW00003) is in range.

Bit 4

Working

velOut

Verifies that the SPEED input (XW00004) is in range.

Bit 5

Working

axisInErr

Goes high for one scan if Axis input is out of range.

Bit 7

OUT

Running

Directly controls YB000000 (Running Output)

Bit 8

OUT

done

Directly controls YB000001 (Complete Output)

Bit 9

OUT

Mistake

Directly controls YB000002 (BlkFault Output)

Bit A

Working

osExecute

Reserved

Bit B

Working

firstPass

One shot coil for initializing block on the rising edge of the
Execute bit.