TECHNICAL NOTE

<ALRMRST> Block Error Condition:

The following table outlines several situations that may cause an error, and will turn on
the blocks “Error” output bit.

Internal Fault Bit

Cause

Note

axisout
AB00000C

Axis specified by
user is out of
range

Valid range is 1 to 16. Will not write to
RDA

Time-out
AB00000D

Alarm condition did
not clear within
default timeout
(500msec).

Alarm condition may still exist. Will not
write to RDA. May need to cycle power
on controller and servopacks to clear the
error, set-up parameter may be out of
range, or hardware failure may exist.



<ALRMRST> Working Registers

This table outlines the data in the four registers used by the Alarm Reset function block.
There is not usually any need for the user to access any of these bits directly.

Register No

TYPE

Name

Description

AW00000

Bit 0

IN

EXECUTE

EXECUTE input (XB000000)

Bit 8

OUT

DONE

DONE output (YB000000)

Bit 9

OUT

ERROR

ERROR output (YB000001)

Bit A

Working

oneshotA

Rising edge

Bit B

Working

firstPass

Initialize block

Bit C

Working

axisout

Indicates axis input is out of range

Bit D

Working

Time-out

Indicates that the alarm did not reset within a specified
(500msec default) timeout period.

AW00001

Working

Counter

Timer for pausing post reset

AW00002

Working

rdaMult

Value for address offset to locate proper RDA

AW00003

Working

Revision

Revision level for block










File: MP2000_IndividualFunctionDocument_RevC 124/168
Doc Number: eng.MCD.05.101

11/17/2005