TECHNICAL NOTE

<SVON> Block Fault Conditions:

The following table outlines several situations that may cause an error. The block error
can be cleared by the ENABLE bit going low.

Internal error bit

Cause

Attention

rdaError
AB000004

The RDA is not
properly set up.

If Motor Rated Speed (MW3**73) or
Encoder resolution (ML3**74) is not
appropriately set up in the RDA, an error
will occur. Sets bit A of RDA Error ID
(MW3**81) if error state exists.

axisinerr
AB000028

The axis number
entered on the
input is not an
acceptable value

The function blocks can only control 1 to
16 axis. Any value greater or smaller then
this will cause an error. This does not set
the RDA Error ID.

RDA_Error
AB000026

The module or axis
number in the RDA
is not acceptable

RDA module number MW3**83 refers to
the address of Module on the rack, and
can be from 1 to 16. The axis number
MW3**84 refers to the axis location on the
module and can be from 1-16. This
typically would occur if an RDAINIT
function block is not used for that axis.

Servo_Alarm/POWER_OFF
IB**2C0/IB**2C4

Servo Alarm

Servo amplifier fault occurred or main
power lost. Sets RDA Error ID (MW3**81)
bit 6 on if no motor power, and bit 7 if
there is a servo alarm.

<SVON> Working Register

This table outlines the data in the forty-five registers used by the function block. There
is not usually any need for the user to access any of these bits directly.

Register No

TYPE

Name

Content

AW00000

Bit

0

IN。

Enable

ENABLE

input (XB000000)

Bit

1

IN。

posEnable

POSENABL

input (XB000001)

Bit

2

IN。

negEnable

NEGENABL

input (XB000002)

Bit

3

IN。

Normal

Servo has main power (IB**2C4), no servo alarm (IB**2C0), and
motion controller is ready (IB**000)

Bit

4

IN。

rdaError

Goes high if the RDA registers are not set properly

Bit

5

Moving

High when motion is commanded

Bit

6

OUT。

rotary

Goes high if RDA calls for Rotary mode

Bit

7

OUT。

State

Directly controls YB000000 (STATUS Output). Must be normal
(AB000003), Servo on must be true (IB**002), and filter set
must be on (AB00002C).

Bit

9

OUT。

Mistake

Directly controls YB000001 (ERROR Output)

Bit A

Working

osEnable

Reserved

Bit B

Working

firstPass

One shot coil for initializing Axis and block on for the rising edge
of enable input

Bit C

Working

osDisable

Reserved

AW00001

Working

Filter

Rreserved.

AW00002

File: MP2000_IndividualFunctionDocument_RevC 110/168