TECHNICAL NOTE

<ASCIIIN> Block Fault Conditions:

The following table outlines several situations that may cause an error. The block error
can be cleared by the EXECUTE bit going low.

Internal Fault Bit

Cause

Note

rcverror
AB00001F

MSG-RCV has an
error.

The MSG-RCV internal function has an
error. Refer to ERROR-ID output for
value.
81= Function code error
82= Address set error
83= Data size error
84= Line number setting error
85= Channel number error
86= Station Address error
88= Transmission unit error
89= Device selection error


<ASCIIIN> Working Registers

This table outlines the data in the Thirty registers used by the function block. There is
not usually any need for the user to access any of these bits directly. The MSG-RCV
type registers can be further understood by referencing the MSG-RCV function block in
the on line help.

Register No.

Type

Name

Description

AW00000

Bit 0

IN

execute

EXECUTE

input (XB000000)

Bit 7

OUT

running

Directly controls YB000000 (RUNNING Output)

Bit 8

OUT

done

Directly controls YB000001 (COMPLETE Output)

Bit 9

OUT

error

Directly controls YB000002 (ERROR Output)

Bit A

Working

oneshotA

Reserved

Bit B

Working

firstPass

One shot on rising edge of EXECUTE input to initialize axis.

AW00001

MSG-RCV

Reserved

Reserved

AW00002

MSG-RCV

Reserved

Reserved

AW00003

MSG-RCV

slave

Called station # (Param2)

AW00004

MSG-RCV

Reserved

Reserved

AW00005

MSG-RCV

Reserved

Reserved

AW00006

MSG-RCV

startAdd

Data address (Param05)

AW00007

MSG-RCV

size

Data size (Param06)

AW00008

MSG-RCV

called_CPU

Called CPU# (Param7)

AW00009

MSG-RCV

Reserved

Reserved