5.5 Program Control Instructions

5.5.4 Direct Input String (INS)

5-82

„

Parameter Table Configuration

The following table gives details about the parameters in the MP2000-series Controller.

∗ If a channel for which the allocation has been deleted in the AI Module detailed definition is specified for the INS

instruction, the applicable channel number is output for the bit. This is because it is not possible to read the data on
channels for which allocations have been deleted.
The relation between bits and channels is shown below.
Bit 0: Channel 1
Bit 1: Channel 2
Bit 2: Channel 3
Bit 3: Channel 4
Bit 4: Channel 5
Bit 5: Channel 6
Bit 6: Channel 7
Bit 7: Channel 8

Address

Data

Type

Symbol

Name

Specification

I/O

0

W

RSSEL

Unit selection 1

Specify the Module to input from.

IN

1

W

MDSEL

Unit selection 2

IN

2

W

STS

Status

Each bit receives the input status for one word.
0: Normal, 1: Error

OUT

3

W

N

Number of words

Specify the number of continuous words.

IN

4

W

ID1

Input data 1

Receives the data that was input.
Contains 0 if an error occurs.

OUT

:

:

:

:

:

N + 3

W

IDN

Input data N

OUT

Module Name

Parameter

CPU (IO)

LIO-01/02 (LIO)

LIO-04/05

(LIO32)

LIO-06

(MIXIO)

AI-01

(AI)

RSSEL

Specify the rack, slot, and subslot of the target Module.
Hexadecimal notation: zxyy hex
x: Rack number from 1 to 4
yy: Slot number from 0 to 9
z: Subslot number from 1 to maximum value (determined by Module specifications)

MDSEL

0 (Not used.)

0 (Not used.)

Offset: 0 or 1

Channel number
- 1: 0 or 1

Channel number
- 1: 0 to 7

STS

Always 0.

Always 0.

Always 0.

Always 0.

*

N

1

1

1 or 2
– MDSEL

1 or 2
– MDSEL

1 to 8
– MDSEL