5.10 System Function Instructions

5.10.6 Send Message (MSG-SND)

5-244

„

 

Status (PARAM01)

The status of the communications section is output to this parameter.
The bit assignments are shown in the following figure.

1.

COMMAND

The abbreviations and meanings of the commands are given in the following table.

2.

RESULT

The abbreviations and meanings of the results are listed in the following table.

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

REQUEST

RESULT

COMMAND

PARAMETER

4

2

1

3

Code

Abbreviation

Meaning

1

U_SEND

Sends a general-purpose message.

2

U_REC

Receives a general-purpose message.

3

ABORT

Aborts operation.

8

M_SEND

Sends a MEMOBUS command and ends when a response is
received.

9

M_REC

Receives a MEMOBUS command and returns a response.

C

MR_SEND

Sends a MEMOBUS response.

Code

Abbreviation

Meaning

0

Execution is in progress.

1

SEND_OK

The send was completed normally.

2

REC_OK

The reception was completed normally.

3

ABORT_OK

Aborting was completed.

4

FMT_NG

A parameter format error occurred.

5

SEQ_NG or
INIT_NG

A command sequence error occurred or a token was not received.
There is no connection to a communications system.

6

RESET_NG or
O_RING_NG

A reset status exists.
Out of ring: A token was not received within the token monitoring
time.

7

REC_NG

A data reception error occurred. (An error was detected in a low-
level program.)