Yaskawa MP900 Series Ladder Programming Manual User Manual

Page 221

Advertising
background image

5.8 DDC Instructions

5.8.5 PD Control (PD)

5-152

[ b ] Parameter Table Configuration for PD Instruction with Real Numbers

∗ The relay input and output bit assignments are the same as for integers.

[ c ] Internal Operation of the Instruction

The deviation X input is used to calculate the PD compensation output as shown below.
In the formula shown below, X’ is the previous input value of X, Ts is the scan time set value, and Td* is the differen-
tial time.

∗ The differential time (Td) is Td1 when X – X’ and X’ have the same sign, and Td2 when X – X’ and X’ have dif-

ferent signs.

P compensation = Upper/lower limit (UL or LL) of (Kp

× X)

D compensation = Kd

× (X

X’)

× Upper/lower limit (IUL or ILL) of

PD compensation = Upper/lower limit (UL or LL) of (P compensation + D compensation) and Dead zone A
(Width DB)

Address

Data

Type

Symbol

Name

Specification

I/O

0

W

RLY

Relay I/O

Relay inputs and relay outputs

*

IN/OUT

1

W

(Reserved.)

Spare register

2

F

Kp

P gain

Gain for the P compensation

IN

4

F

Kd

D gain

Gain for the input to the differential circuit

IN

6

F

Td1

Differential time for
divergence

Differential time used when the input diverges (s)

IN

8

F

Td2

Differential time for
convergence

Differential time used when the input converges (s)

IN

10

F

UL

PD upper limit

Upper limit for the P + D compensation

IN

12

F

LL

PD lower limit

Lower limit for the P + D compensation

IN

14

F

DB

PD output dead zone

Dead zone width for the P + D compensation

IN

16

F

Y

PD output

PD compensation output (output to Out)

OUT

18

F

X

Input value storage

Storage of current input value

OUT

Td

Ts

Advertising
This manual is related to the following products: