3 ) programming example – Yaskawa MP900 Series Ladder Programming Manual User Manual

Page 79

Advertising
background image

5.2 Relay Circuit Instructions

5.2.4 10-ms OFF-Delay Timer (TOFF[10ms])

5-10

( 3 ) Programming Example

In the following programming example, the set value of the TOFF instruction is 50, and the count value is stored in the
DW00001 register.
The DB000001 coil will turn OFF after the DB000000 relay stays OFF for 500 ms.

The timing chart is shown below.

DW00001

50

0

500 ms - Ts

(Ts: Scan time set value)

DB000000

DB000001

ON
OFF

ON
OFF