5.9 Table Manipulation Instructions

5.9.7 Read Queue Table (QTBLR and QTBLRI)

5-217

Instructions

5

[ a ] Parameter Table Configuration

[ b ] Error Codes

[ c ] Setting the Relative Row Numbers of Table Elements

( 3 ) Programming Example

In the following programming example, the specified column elements in array table data TBL1 are read and stored in
MW00010 to MW00012 when switch 2 (DB000002) turns ON.
Before switch 2 is turned ON, the table data is set as shown below by turning ON switch 1 three times while changing
the contents of MW00000 to MW00002. (Refer to information on the Write Queue Table instruction.)

The contents of table data TBL1 are given below.

Œ

The column data types are given in parentheses.

Address

Data

Type

Symbol

Name

Specification

I/O

0

L

ROW

Relative row number of
table elements

Relative row number of table elements at source to
move (1 to 65,535)

IN

2

L

COLUMN

First column number of
table elements

First column number of table elements at source to
move (1 to 32,767)

IN

4

W

CLEN

Number of column ele-
ments

Number of column elements to move (1 to 32,767)

IN

5

W

Reserved.

6

L

RPTR

Read pointer

Read pointer of the queue after execution

OUT

8

L

WPTR

Write pointer

Write pointer of the queue after execution

OUT

Error Code

Error Name

Meaning

0001 hex

Table undefined

The target table is undefined.

0002 hex

Outside range of row numbers

The row number of the table element is outside the target table.

0003 hex

Outside range of column num-
bers

The column number of the table element is outside the target table.

0004 hex

Incorrect number of elements

The number of target elements is invalid.

0005 hex

Insufficient storage area

The storage area is insufficient.

0006 hex

Insufficient element type

The data type specified for the element is wrong.

0007 hex

Queue buffer error

An attempt was made to read from an empty queue buffer, or to write to a
full queue buffer by advancing the pointer.

0008 hex

Queue table error

The specified table is not a queue table.

0009 hex

System error

An unexpected error was detected in the system during instruction execu-
tion.

Relative Row

Number

Row That Is Read

Remarks

0

Read pointer row

The pointer is advanced only for the QTBLRI instruction.

1

Read pointer row

Pointer is not advanced.

2

Read pointer row – 1

Pointer is not advanced.

3

Read pointer row – 2

Pointer is not advanced.

:

:

n

Read pointer row – (n – 1)

Pointer is not advanced.

Column

Row

1

(W)

2

(W)

3

(W)

1

11

12

13

2

21

22

23

3

31

32

33