5.10 System Function Instructions
5.10.8 Write Inverter Parameter (ICNS-WR)
5-264
( 3 ) Programming Example
In the following programming example, the data in MW00000 is written to parameter Bn-10 in the Inverter that is con-
nected as station 1 to the SVB-01 on circuit 1.
When DB000000 turns ON, the parameter is written to the Inverter.
After execution, you must check the Complete bit (DB000003) to make sure that it has turned ON, and then write the
data to parameter storage memory in the Inverter (EEPROM). (Refer to ( 4 ) Additional Information.)